6. Module programming and commissioning:
see Software MEKM.
Important:
If the presence detection is used together with radio data transmission, there must be a distance of at least 70 cm between the radio module and the presence detection in order to rule out interference
Antenna
RFID Antenna
The antenna captures the transponder data in the
reading range up to approx. 20 mm and forwards
it to the evaluation electronics.
Only when the authorisation has been recognized,
the release switch then switches the connected
load.
Bluetooth Antenna
„Bluetooth classic“
Radio range approx. 10 to 50 meters.
Technical data
Dimensions without connection cable | Diameter x Length:: Ø 38 x 58 mm Drilling diameter: Ø 30 mm Thread: Ø 30 x 1 mm, 14 mm long |
Weight without connection cable | 40 g |
Casing | transparent, protection IP 54, accord. To DIN EN 60529 |
Attachment | Screw connection with nut Ø 30 x 1 mm |
Temperature range | –10 to +65 °C |
Working relay | Signal „Driver logged in“ Potential free close-contact of MEK, Max. Load of the contacts in MEK 12 V: 2 A / 24 W | 24 V: 2 A / 48 W | 48 V: 1,25 A / 60 W • Open: Forklift out of service, NOT permitted to drive or lift • Closed: Forklift in use, permitted to drive or lift |
Entry presence detection | Plus 5 up to 120 V DC GND 0 up to > 1 V DC |
Lenght of connection cable | 2 meters |
On – and Off switch | Via user transponder, display with LEDs |
Power supply | Nominal battery voltage: 12 – 48 V DC |
Power consumption / performance | < 150 mA < 3 W |
Programming of user data | Bluetooth |
Transponder | 125 kHz
|
Response range of the transponder | Up to approx. 20 mm |
Data receipt | Battery-backed (5 years battery life) |
Certificate | CE EMV DIN EN 12895 |
Troubleshooting
Measure voltage input
Measure the brown and pink cable. There must be at least 12 V DC.
Check presence detection
Measure at the yellow cable. It must be the set potential. Or internally move the smart lock,
the blue LED must light up.
Check working relay
Remove cable from Pin 4 and Pin 5. Perform continuity measurement:
Logged out: No continuity (contact open, high resistance).
Logged in: Passage (contact closed, approx. 0 Ohm).
...