6. Module programming and commissioning:
see Software MEKM.


Important:

If the presence detection is used together with radio data transmission, there must be a distance of at least 70 cm between the radio module and the presence detection in order to rule out interference


Antenna

RFID Antenna
The antenna captures the transponder data in the
reading range up to approx. 20 mm and forwards
it to the evaluation electronics.
Only when the authorisation has been recognized,
the release switch then switches the connected
load.

Bluetooth Antenna
„Bluetooth classic“
Radio range approx. 10 to 50 meters.


Technical data

Dimensions without connection cableDiameter x Length:: Ø 38 x 58 mm
Drilling diameter: Ø 30 mm
Thread: Ø 30 x 1 mm, 14 mm long
Weight without connection cable40 g
Casingtransparent, protection IP 54, accord. To DIN EN
60529
AttachmentScrew connection with nut Ø 30 x 1 mm
Temperature range–10 to +65 °C
Working relaySignal „Driver logged in“
Potential free close-contact of MEK, Max. Load of the contacts
in MEK
12 V: 2 A / 24 W | 24 V: 2 A / 48 W | 48 V: 1,25 A / 60 W
• Open: Forklift out of service, NOT permitted to drive or lift
• Closed: Forklift in use, permitted to drive or lift
Entry presence detectionPlus 5 up to 120 V DC
GND 0 up to > 1 V DC
Lenght of connection cable2 meters
On – and Off switchVia user transponder, display with LEDs
Power supplyNominal battery voltage: 12 – 48 V DC
Power consumption / performance< 150 mA
< 3 W
Programming of user dataBluetooth
Transponder

125 kHz
❙❙ EM4100/4102/4200 (Unique – Standard Mobile
Easykey Transponder)
❙❙ EM4150, EM4450
❙❙HITAG 1
❙❙HITAG 2
❙❙HITAG S
❙❙HID Proximity


13,56 MHz
❙❙MIFARE Classic
❙❙MIFARE DESFire
❙❙ LEGIC prime
❙❙ LEGIC advant

Response range of the transponderUp to approx. 20 mm
Data receiptBattery-backed (5 years battery life)
CertificateCE
EMV DIN EN 12895


Troubleshooting


Measure voltage input
Measure the brown and pink cable. There must be at least 12 V DC.
Check presence detection
Measure at the yellow cable. It must be the set potential. Or internally move the smart lock,
the blue LED must light up.
Check working relay
Remove cable from Pin 4 and Pin 5. Perform continuity measurement:
Logged out: No continuity (contact open, high resistance).
Logged in: Passage (contact closed, approx. 0 Ohm).

...